What is an amine corrosion inhibitor?
It is a corrosion inhibitor based on amine chemistry. Neutralising amines raise condensate pH by countering carbonic acid, and filming amines form a barrier on the metal surface. Pipeline film-forming inhibitors work in a similar way in oil and gas lines.
Read more →
Do neutralizing amines remove dissolved oxygen?
No. Neutralising amines raise pH, but they do not scavenge oxygen. Dissolved oxygen needs deaeration or a treatment that reacts with oxygen, and without one, oxygen corrosion can carry on at acceptable pH.
Read more →
Can CI 3023 replace a boiler corrosion inhibitor?
No. CI 3023 is documented as a film-forming inhibitor for oil and gas production and pipeline transport. Its published data does not establish amine composition, steam volatility or suitability for boiler water or steam condensate.
Read more →
Why can condensate corrosion continue when receiver pH looks acceptable?
An amine splits between steam and water, so it may protect the lines near the receiver while far lines stay unprotected. Oxygen and other contaminants can also keep corrosion going at acceptable pH, so sample at remote points as well.
Read more →
How is corrosion inhibitor dosage determined?
For pipelines, the dose is based on transported-fluid flow. The published CI 3023 starting range is 6-12 g/m³, confirmed with laboratory tests, coupons or probes. Condensate amine dosage depends on acid loading, distribution and recycling. Refer to our TDS for the exact figure.
Read more →